4-20 mA Two-Wire Current Loop Basics
Many Gems sensors products offer a linear 4-20 milliamp (mA) output signal for transmitting to a receiver (meter/display, PLC, etc.) when measuring level or pressure. It is good to know the basics when troubleshooting or when choosing the best output signal for your application.
The most commonly used output for transmitting a linear signal is the two-wire 4-20 mA output. Its popularity is due to several beneficial properties. Using the current loop is a good option for long distance transmission. First, the accuracy of the signal is not affected by interconnected wiring over long distances with different conductors. Next, it allows for transmitting to several receivers wired in series in the loop as long as there is sufficient voltage supply to power all the devices (while not exceeding transmitter maximum voltage rating). Also, current loops make troubleshooting easier because you know that the input current you are reading at your PLC or display meter is the same value that is coming from your sensor or transmitter.
Another troubleshooting bonus when using the 4-20 mA current loop is the zero offset being at 4 mA instead of at 0 mA. Having the “zero-signal” actually be at 4 mA helps to more easily recognize failures due to a sensor lead break or open device. For instance, with a 0-20 mA current loop, there would be no immediate way to know if your 0mA signal was an actual zero-signal output or a broken wire.
Current loops are less sensitive to electrical noise than voltage transmission, and because it can transmit using very small DC voltages, it is also less likely to induce electrical noise emission to other conductors or equipment.
A 4-20 mA two-wire current loop in its most basic configuration consists of 4 components:

- Power supply
- Transmitter (or sensor)
- Receiver (meter, PLC, etc.)
- Conductor (wire)
Some things to note concerning the components of a 4-20 mA two-wire current loop; It use DC power, and the current source comes from the power supply (not the transmitter or sensor). The level of DC voltage supplied must be enough to drive all components in the loop while staying within their individual min/max voltage ranges. The transmitter/sensor translates the real-world condition (e.g. level, temperature, pressure) into the 4-20mA signal used by the receiver. The receiver scales the process variable range to match the 4-20 input providing a minimum and maximum value. You should also pay attention to the wire resistance and total impedance of the loop, especially in long distance applications.
Information from Gems Sensors
相关推荐
- 螺纹的一般知识
- 螺纹知识:美国标准管螺纹(美制)
- Anfield Sensors T200 / T201系列 - 紧凑型压力变送器
- 树木年轮显示 2023 年是 2000 年来最热的夏天
- Tree Rings Reveal 2023 Was the Hottest Summer in 2,000 Years
- 全球传感器产业最富有的女性
- 美国setra西特空压机压力传感器
- 英国Gems捷迈压力变送器怎么样
- Dòng CSP63 có một số lượng lớn các máy phát áp suất cao chương trình
- CSP63 Series High Pressure Large Range Pressure Transducers